Air conditioners and heat pumps
Bans:
Self-contained systems < 12 kW: >GWP 150 from 2027
Self-contained systems < 12 kW: Ban on F-gases from 2032
Self-contained systems 12-50 kW: >GWP 150 from 2027
Self-contained systems > 50 kW: >GWP 150 from 2030
Split units with <3kg filling quantity: >GWP 750 from 2025
Split units < 12 kW (air-water): >GWP 150 from 2027
Split units < 12 kW (air-air): >GWP 150 from 2029
Split units < 12 kW: Ban on F-gases from 2035
Split units > 12 kW: >GWP 750 from 2029
Split units > 12 kW: >GWP 150 from 2033
Stationary refrigeration systems
Bans:
Household appliances: Ban on F-gases from 2026
Commercial refrigerators and freezers: >GWP 150 from 2025
Other self-contained refrigeration systems: >GWP 150 from 2025
Stationary refrigeration systems (except chillers): >GWP 2500 from 2025
Stationary refrigeration systems (except chillers): >GWP 150 from 2030
Chillers < 12 kW: >GWP 150 from 2027
Chillers < 12 kW: Ban on F-gases from 2032
Chillers > 12 kW: >GWP 750 from 2027
Comments